|
This article is cited in 4 scientific papers (total in 4 papers)
Short Communications
Heat transfer in a water flow in tubes with ribbed twisted tape inserts
A. A. Giniyatullin, S. È. Tarasevich, A. B. Yakovlev Kazan State Technical University
Abstract:
The results of an experimental study of heat transfer in a water flow in a channel with a twisted tape insert with discrete ribs installed at an angle to the tape axis are presented. The experiments were performed in a straight smooth tube with an inner diameter of $10$ mm. The tape inserts had a twist ratio of $2.5$, $3$, or $4$ with a $180^{\circ}$ rotation; the rib height ranged from $0.5$ to $1.5$ mm, the rib pitch was from $40$ to $120$ mm, and the rib angle was from $40$ to $50^{\circ}$ to the tape axis. The results of experiments in the mentioned range of geometries suggest that the ribbed tape inserts increase heat transfer by a maximum of $40\%$ as compared with that in tubes with a twisted tape without ribs. The generalized correlation is given for the prediction of heat transfer in a Reynolds number range $\rm Re = 10^4$–$2 \times 10^5$.
Received: 04.07.2016 Accepted: 18.04.2017
Citation:
A. A. Giniyatullin, S. È. Tarasevich, A. B. Yakovlev, “Heat transfer in a water flow in tubes with ribbed twisted tape inserts”, TVT, 56:2 (2018), 313–316; High Temperature, 56:2 (2018), 302–305
Linking options:
https://www.mathnet.ru/eng/tvt10725 https://www.mathnet.ru/eng/tvt/v56/i2/p313
|
Statistics & downloads: |
Abstract page: | 223 | Full-text PDF : | 130 | References: | 25 |
|