Journal of Siberian Federal University. Mathematics & Physics, 2015, Volume 8, Issue 2, Pages 201–207
(Mi jsfu422)
|
|
|
|
This article is cited in 11 scientific papers (total in 11 papers)
Adaptive identification method of a signal from stray magnetic field sensor for turbogenerator diagnostics
Vladimir I. Polishchuk, Viktor L. Sergeev National Research Tomsk Polytechnic University,
Lenin Av., 30, Tomsk, 634050, Russia
Abstract:
The topic of this paper is dictated by the necessity to improve the reliability of methods for determining a short circuit of rotor winding with the use of the stray magnetic field sensor installed at the turbogenerator end.
The research objectives are to develop the signal identification models and algorithms based on stray magnetic field sensor data for the diagnostics of a short circuit of rotor winding of synchronous generator.
Theoretical and practical developments in the areas of systems analysis, electrical machines modeling, optimization and linear algebra are used in the paper. The solution is based on theoretical and experimental data from magnetic field sensor installed at the synchronous generator end.
A method of a signal identification and diagnostics from stray magnetic field sensor installed at the synchronous generator end is developed. This method is based on an integrated system of signal models with time-varying parameters and additional a priori information. The method allows for determining the signal local changes from the stray magnetic field sensor caused by the short circuit of rotor winding of the synchronous generator by comparing the original signal with model signal. Experimental data for loaded synchronous generator are considered. It is found that the proposed method provides reliable predictions of the rotor winding damage even for a small number of short circuited coils.
Keywords:
identification, adaptation, diagnostics, integrated system of models with variable parameters, a priori information, turbogenerator, short circuit, magnetic field sensor.
Received: 10.12.2014 Received in revised form: 21.01.2015 Accepted: 20.02.2015
Citation:
Vladimir I. Polishchuk, Viktor L. Sergeev, “Adaptive identification method of a signal from stray magnetic field sensor for turbogenerator diagnostics”, J. Sib. Fed. Univ. Math. Phys., 8:2 (2015), 201–207
Linking options:
https://www.mathnet.ru/eng/jsfu422 https://www.mathnet.ru/eng/jsfu/v8/i2/p201
|
Statistics & downloads: |
Abstract page: | 267 | Full-text PDF : | 76 | References: | 62 |
|